Web Orders Over $100 Ship Free. Enter Promo Code "SHIPFREE" for free UPS Ground Shipping at Checkout. (USA Only)

ROTAS Programmable Rotational Speed Monitor

Click images to enlarge.
The ROTAS programmable speed monitor measures the roational speed of machines and systems. It detects the signals of most non-contact speed and motion sensors such as Hall effect, magneto-inductive, magneto-resistive and others. If the measured value exceeds or falls below a preset limit value the alarm relay is automatically switched. The following types of conditions are typically monitored.

Over speed monitoring with reset switching delay
An over speed condition triggers the alarm relay. Once the speed has fallen below the hysteresis value and the rest time delay has expired, the alarm relay resets to normal.

Under speed monitoring with run-up delay
An under speed condition triggers the alarm relay. Monitoring does not start until after the signal of the external start trigger has de-energized and the starting delay time has elapsed.

Remote speed monitoring using the analog output
The analog output can be used to remotely monitor machinery rotational speed. This combined with the alarm functions provides an economical soulution for your speed monitoring applications.

Industry Applications
The speed monitor has numerous applications in many areas of the technology, whether it be for protection of personnel, machines or manufactured products, to ensure that a plant operates at optimum efficiency, or for speed-dependent switching of system functions in a process.

Specifications

General Specifications
Frequency Range 0.01 Hz to 20,000 Hz, 36V max
Units Hz, pulses/min, pulses/hr, rpm, in/sec, in/min, in/hr, ft/sec, ft/min, ft/hr, mph, meters/sec, meters/min, meters/hr, km/hr
Pulses per Unit 1 to 10,000
Input Averaging 1-255 pulses depending on relay 1 setting
Accuracy ±0.03% of full scale ±1 digit
Temperature Coefficient ±0.01% of full scale
Power 18 to 36 VDC, less than 160 mA
Sensor Specifications
Types PNP, NPN, or sine wave, 2- or 3-wire
Minimum Pulse 20 µs duration
Sensor Supply 12 VDC, 60 mA max.
Trigger Level Ranges NPN & PNP: 2.5 to 6V 10 kΩ imp.
Sine wave: 1.0 to 2.5V 100 kΩ imp.
Others: 0.2 to 0.7V 100 kΩ imp.
Trigger Level Defaults NPN & PNP: 6V
Sine wave: 2.5V
External Start Input >2.5 to 36V to start, <1.0V to stop
Relay Output
CR and CRA One SPDT relay
CRR and CRRA Two SPDT relays
Response Time <20 milliseconds + measuring period
Relay Action Programmable Hi/Lo and normal/reverse
Contact Rating 5 A @ 250 VAC max. resistive load or
2 A @ 42 VDC max. resistive load
Hysteresis Adjustable 1 to 85% of full scale units
Alarm Reset Delay Adjustable 0-99.9 seconds
Relay 1, Hi alarm mode only
Alarm Trigger Delay Adjustable 0-99.9 seconds
Relay 1 or 2, Lo alarm mode only
Analog Output
Ranges 0-20 mA or 4-20 mA
Accuracy ±1.0% of full scale
Maximum Burden 400 Ω
Temperature Coefficient ±0.02% of full scale
Environmental and Mechanical Specifications
Operating Temperature –25 to 70°C (–13 to 158°F)
Protection (IEC 529) IP 20 (installation in enclosure)
Vibration (IEC 68-2-6) 0.7 G @ 1-100 Hz
Dimensions 43 mm x 70 mm x 114 mm (W, H, D)
Material UL94-V-0 polycarbonate
Mounting Standard 35 mm DIN-rail
Model Output Power
CR 1 Relay 18-36 VDC
CRR 2 Relays 18-36 VDC
CRA 1 Relay, Analog Output 18-36 VDC
CRRA 2 Relays, Analog Output 18-36 VDC