Over speed monitoring with reset switching delay
An over speed condition triggers the alarm relay. Once the speed has fallen below the hysteresis value and the rest time delay has expired, the alarm relay resets to normal.
Under speed monitoring with run-up delay
An under speed condition triggers the alarm relay. Monitoring does not start until after the signal of the external start trigger has de-energized and the starting delay time has elapsed.
Remote speed monitoring using the analog output
The analog output can be used to remotely monitor machinery rotational speed. This combined with the alarm functions provides an economical soulution for your speed monitoring applications.
Industry Applications
The speed monitor has numerous applications in many areas of the technology, whether it be for protection of personnel, machines or manufactured products, to ensure that a plant operates at optimum efficiency, or for speed-dependent switching of system functions in a process.
General Specifications | ||
---|---|---|
Frequency Range | 0.01 Hz to 20,000 Hz, 36V max | |
Units | Hz, pulses/min, pulses/hr, rpm, in/sec, in/min, in/hr, ft/sec, ft/min, ft/hr, mph, meters/sec, meters/min, meters/hr, km/hr | |
Pulses per Unit | 1 to 10,000 | |
Input Averaging | 1-255 pulses depending on relay 1 setting | |
Accuracy | ±0.03% of full scale ±1 digit | |
Temperature Coefficient | ±0.01% of full scale | |
Power | 18 to 36 VDC, less than 160 mA | |
Sensor Specifications | ||
Types | PNP, NPN, or sine wave, 2- or 3-wire | |
Minimum Pulse | 20 µs duration | |
Sensor Supply | 12 VDC, 60 mA max. | |
Trigger Level Ranges |
NPN & PNP: 2.5 to 6V 10 kΩ imp. Sine wave: 1.0 to 2.5V 100 kΩ imp. Others: 0.2 to 0.7V 100 kΩ imp. |
|
Trigger Level Defaults |
NPN & PNP: 6V Sine wave: 2.5V |
|
External Start Input | >2.5 to 36V to start, <1.0V to stop | |
Relay Output | ||
CR and CRA | One SPDT relay | |
CRR and CRRA | Two SPDT relays | |
Response Time | <20 milliseconds + measuring period | |
Relay Action | Programmable Hi/Lo and normal/reverse | |
Contact Rating |
5 A @ 250 VAC max. resistive load or 2 A @ 42 VDC max. resistive load |
|
Hysteresis | Adjustable 1 to 85% of full scale units | |
Alarm Reset Delay |
Adjustable 0-99.9 seconds Relay 1, Hi alarm mode only |
|
Alarm Trigger Delay |
Adjustable 0-99.9 seconds Relay 1 or 2, Lo alarm mode only |
|
Analog Output | ||
Ranges | 0-20 mA or 4-20 mA | |
Accuracy | ±1.0% of full scale | |
Maximum Burden | 400 Ω | |
Temperature Coefficient | ±0.02% of full scale | |
Environmental and Mechanical Specifications | ||
Operating Temperature | –25 to 70°C (–13 to 158°F) | |
Protection (IEC 529) | IP 20 (installation in enclosure) | |
Vibration (IEC 68-2-6) | 0.7 G @ 1-100 Hz | |
Dimensions | 43 mm x 70 mm x 114 mm (W, H, D) | |
Material | UL94-V-0 polycarbonate | |
Mounting | Standard 35 mm DIN-rail | |
Model | Output | Power |
CR | 1 Relay | 18-36 VDC |
CRR | 2 Relays | 18-36 VDC |
CRA | 1 Relay, Analog Output | 18-36 VDC |